Data Sheet

Forcing
● Forcing
Yes
● Forcing, variables
Inputs/outputs, bit memories, distributed I/Os
● Number of variables, max.
256
Diagnostic buffer
● present
Yes
● Number of entries, max.
3200
— adjustable
Yes
— preset
120
Service data
● can be read out
Yes
EMC
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas
Yes
● Limit class B, for use in residential areas
No
Standards, approvals, certificates
CE mark Yes
Ambient conditions
Ambient temperature during operation
● min.
-25°C; = Tmin
● max.
70°C; = Tmax; @ 60°C for UL/ATEX/FM and safety-related
application
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ...
+5 000 m); with "F-System" applications max. +2 000 m above
sea level permissible
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according
to EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 3B3 on request
— to chemically active substances according
to EN 60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
6AG1412-5HK06-7AB0 Subject to change without notice
Page 12/
14
09/13/2019 © Copyright Siemens