Data Sheet

Output current
● for signal "1" rated value
0.5A
● for signal "1" permissible range, min.
5mA
● for signal "1" permissible range, max.
0.6A
● for signal "0" residual current, max.
0.3mA
Switching frequency
● with resistive load, max.
100Hz
● with inductive load, max.
0.5Hz
Total current of the outputs (per group)
all mounting positions
— up to 60 °C, max.
2A; 8 adjacent outputs each
Cable length
● shielded, max.
1000m
● unshielded, max.
600m
Interrupts/diagnostics/status information
Diagnostics function No
Potential separation
Potential separation digital outputs
● between the channels, in groups of
32
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 500 V DC
Ambient conditions
Ambient temperature during operation
● min.
-25°C; = Tmin
● max.
60°C; = Tmax
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
Resistance
Use in stationary industrial systems
6AG1422-1BL00-2AA0 Subject to change without notice
Page 2/
3
09/13/2019 © Copyright Siemens