— Number of external encoders, max.
6; Requirement: There must be no other motion technology
objects created; note: The number of axes affects the cycle time
of the PLC program; selection guide via the TIA Selection Tool
Controller
● PID_Compact
Yes; Universal PID controller with integrated optimization
● PID_3Step
Yes; PID controller with integrated optimization for valves
● PID-Temp
Yes; PID controller with integrated optimization for temperature
Counting and measuring
● High-speed counter
Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-40°C; = Tmin (incl. condensation/frost); start-up @ -20 °C
● horizontal installation, max.
70°C; Display: 50 °C, at an operating temperature of typically 50
°C, the display is switched off
● vertical installation, min.
-40°C; = Tmin; Startup @ -20 °C
● vertical installation, max.
40°C; Display: 40 °C, at an operating temperature of typically 40
°C, the display is switched off
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation / frost (no commissioning in
bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available
coolants and lubricants
Yes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according
to EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 3B3 on request
— to chemically active substances according
to EN 60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-3
Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according
to EN 60721-3-6
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class
6B3 on request