Data Sheet
Digital outputs
Type of digital output Relays
Number of digital outputs 8
Digital outputs, parameterizable Yes
Controlling a digital input possible
Size of motor starters according to NEMA, max. 5
Switching capacity of the outputs
● on lamp load, max.
1500W; 10 000 operating cycles
● Low energy/fluorescent lamps with electronic
control gear
10x 58 W (25 000 operating cycles)
● Fluorescent tubes, conventionally compensated
1x 58 W (25 000 operating cycles)
● Fluorescent tubes, uncompensated
10x 58 W (25 000 operating cycles)
Output current
● for signal "1" rated value
5A
● for signal "1" permissible range, min.
5mA; 10 V
● for signal "1" permissible range, max.
8A; thermal continuous current
● for signal "0" residual current, max.
0A
Parallel switching of two outputs
● for logic links
Yes
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
2Hz
● with inductive load, max.
0.5Hz
● on lamp load, max.
2Hz
Total current of the outputs
● Current per channel, max.
8A; Note derating data in the manual
● Current per group, max.
8A; Note derating data in the manual
● Current per module, max.
64A; Note derating data in the manual
Relay outputs
● Number of relay outputs
8
● Rated supply voltage of relay coil L+ (DC)
24V
● Current consumption of relays (coil current of
all relays), max.
80mA
● external protection for relay outputs
With miniature circuit breaker with characteristic B for: cos φ 1.0:
600 A cos φ 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1 000 A
● Contact connection (internal)
No
● Number of operating cycles, max.
4000000; see additional description in the manual
● Relay approved acc. to UL 508
Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300
Switching capacity of contacts
— with inductive load, max.
see additional description in the manual
— with resistive load, max.
see additional description in the manual
6AG1522-5HF00-2AB0 Subject to change without notice
Page 2/
5
09/16/2019 © Copyright Siemens