Data Sheet

Reverse polarity protection Yes
Input current
Current consumption, max. 150mA
Power
Power available from the backplane bus 0.8W
Power loss
Power loss, typ. 5W
Digital outputs
Type of digital output Relays
Number of digital outputs 16
Current-sinking Yes
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
Controlling a digital input Yes
Size of motor starters according to NEMA, max. 5
Switching capacity of the outputs
● on lamp load, max.
50 W (230 V AC), 5 W (24 V DC)
Output current
● for signal "1" rated value
2A
● for signal "1" permissible range, min.
10mA; 10 V
● for signal "1" permissible range, max.
2A; thermal continuous current
● for signal "0" residual current, max.
0A
Parallel switching of two outputs
● for logic links
Yes
● for uprating
No
● for redundant control of a load
Yes
Switching frequency
● with resistive load, max.
1Hz
● with inductive load, max.
0.5Hz
● on lamp load, max.
1Hz
Total current of the outputs
● Current per channel, max.
2A; see additional description in the manual
● Current per group, max.
2A; see additional description in the manual
● Current per module, max.
32A; see additional description in the manual
Relay outputs
● Number of relay outputs
16
● Rated supply voltage of relay coil L+ (DC)
24V
● Current consumption of relays (coil current of
all relays), max.
150mA
● external protection for relay outputs
Miniature circuit breaker B10 / B16
6AG1522-5HH00-7AB0 Subject to change without notice
Page 2/
5
09/15/2019 © Copyright Siemens