Data Sheet

Power loss
Power loss, typ. 7W
Analog outputs
Number of analog outputs 8; > +60 °C max. 4x ±10 V permissible
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45mA
Current output, no-load voltage, max. 20V
Cycle time (all channels), min. 125µs; independent of number of activated channels
Output ranges, voltage
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Connection of actuators
● for voltage output two-wire connection
Yes
● for voltage output four-wire connection
Yes
● for current output two-wire connection
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1kΩ
● with voltage outputs, capacitive load, max.
100nF
● with current outputs, max.
500Ω
● with current outputs, inductive load, max.
1mH
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
● Conversion time (per channel)
50µs
● Basic execution time of the module (all
channels released)
125µs
Settling time
● for resistive load
30µs; see additional description in the manual
● for capacitive load
100µs; see additional description in the manual
● for inductive load
100µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to
50 kHz), (+/-)
0.02%
Linearity error (relative to output range), (+/-) 0.15%
Temperature error (relative to output range), (+/-) 0.002%/K
6AG1532-5HF00-7AB0 Subject to change without notice
Page 2/
5
09/15/2019 © Copyright Siemens