Data Sheet
Crosstalk between the outputs, max. -100dB
Repeat accuracy in steady state at 25 °C (relative to
output range), (+/-)
0.05%
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-)
0.4%
● Current, relative to output range, (+/-)
0.4%
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-)
0.2%
● Current, relative to output range, (+/-)
0.2%
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes
Execution and activation time (TCO), min. 100µs
Bus cycle time (TDP), min. 250µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Monitoring the supply voltage
Yes
● Wire-break
Yes; Only for output type "current"
● Short-circuit
Yes; Only for output type "voltage"
● Overflow/underflow
Yes
Diagnostics indication LED
● RUN LED
Yes; Green LED
● ERROR LED
Yes; Red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green LED
● Channel status display
Yes; Green LED
● for channel diagnostics
Yes; Red LED
● for module diagnostics
Yes; Red LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
● Between the channels and load voltage L+
Yes
Permissible potential difference
between MANA and M internally (UISO) 75 V DC/60 V AC
between S- and MANA (UCM) ±8 V
Isolation
6AG1532-5HF00-7AB0 Subject to change without notice