Data Sheet

Impulse voltage resistance, max. 15V
Input for analog temperature sensor Yes
Measuring range
● Temperature for type J thermocouple, min.
0°C
● Temperature for type J thermocouple, max.
650°C
● Temperature for type K thermocouple, min.
0°C
● Temperature for type K thermocouple, max.
440°C
● Temperature for type L thermocouple, min.
0°C
● Temperature for type L thermocouple, max.
640°C
● Temperature for Pt 100 according to IEC
60751, min.
0°C
● Temperature for Pt 100 according to IEC
60751, max.
410°C
● Temperature for Pt 1000 according to IEC
60751, min.
0°C
● Temperature for Pt 1000 according to IEC
60751, max.
850°C
Errors/accuracies
● Measuring accuracy
±1 K
● Temperature drift per °C, typ.
0.05%/°C
● Temperature offset per K, max.
0.1K/K
Connection method
● Design of electrical connection for temperature
sensors
1x 8 pole connector with spring-loaded connection
— Connectable conductor cross-sections for
AWG cables
1x (24 ... 16)
— Connectable conductor cross-sections,
solid
1x (0.2 ... 1.5 mm²)
— Connectable conductor cross-sections with
wire end processing
1x (0.25 ... 1.5 mm²)
Interfaces
Interfaces/bus type system interface
Interrupts/diagnostics/status information
Number of status displays 2
LED status display LED green = Ready, LED red = Error display
Integrated Functions
Measuring functions
● Current measurement
Yes
Measuring inputs for current
— Current measurement range, min.
0mA
— Current measurement range, max.
20mA
— Relative measuring accuracy current
0.5%
6BK1900-0AA00-0AA0 Subject to change without notice
Page 2/
4