Data Sheet

● Design of electrical connection for supply
voltage
Connector, 2-pole + PE
— Connectable conductor cross-sections,
finely stranded with wire end processing
2x (6 ... 25 mm²) and 1x PE (6 ... 16 mm²)
— Connectable conductor cross-sections for
AWG cables
2x (8 ... 4)
Input voltage
Design of the power supply external
Type of voltage DC
Supply voltage for electronics 24V
Relative symmetrical tolerance of the input voltage 20%
Input current
Current consumption for the electronics, max. 0.25A
Power electronics
Type of load Ohmic load
Type of control of the heating elements Half-wave control
Power capacity, max. 25.2kW
Switching capacity current per phase, max. 63A
Breaking capacity maximum short-circuit current (Icu)
at 400 V
25kA
Rated conditional short-circuit current (Iq) 25kA
Heating power
● Number of digital outputs
9
● Number of heating elements per output, max.
1
● Output voltage for heating power
400V
● Power carrying capacity per output, min.
200W
● Power carrying capacity per output, max.
4000W
● Output current for heating power
10A
● Design of short-circuit protection per output
Fuse 15 A
Fan control
● Number of digital outputs
0
Connection method
● Design of electrical connection for main circuit
Connector, 5-pole
● Design of electrical connection at output for
heating and fan
Connector, 20-pole + PE
— Connectable conductor cross-sections,
finely stranded with wire end processing
18x (1.5 ... 4 mm²), 1x PE (1.5 ... 16 mm²)
— Connectable conductor cross-sections for
AWG cables, stranded
18x (18 ... 12)
Interfaces
Interfaces/bus type PROFIBUS DP
PROFIBUS DP
6BK1932-0AA00-0AA0 Subject to change without notice
Page 2/
4