Data Sheet
● Design of electrical connection for supply
voltage
Connector, 2-pole + PE
— Connectable conductor cross-sections,
finely stranded with wire end processing
2x (6 ... 25 mm²) and 1x PE (6 ... 16 mm²)
— Connectable conductor cross-sections for
AWG cables
2x (8 ... 4)
Input voltage
Design of the power supply external
Type of voltage DC
Supply voltage for electronics 24V
Relative symmetrical tolerance of the input voltage 20%
Input current
Current consumption for the electronics, max. 0.25A
Power electronics
Type of load Ohmic load
Type of control of the heating elements Half-wave control
Power capacity, max. 25.2kW
Switching capacity current per phase, max. 63A
Breaking capacity maximum short-circuit current (Icu)
at 400 V
25kA
Rated conditional short-circuit current (Iq) 25kA
Heating power
● Number of digital outputs
9
● Number of heating elements per output, max.
1
● Output voltage for heating power
400V
● Power carrying capacity per output, min.
200W
● Power carrying capacity per output, max.
4000W
● Output current for heating power
10A
● Design of short-circuit protection per output
Fuse 15 A
Fan control
● Number of digital outputs
0
Connection method
● Design of electrical connection for main circuit
Connector, 5-pole
● Design of electrical connection at output for
heating and fan
Connector, 20-pole + PE
— Connectable conductor cross-sections,
finely stranded with wire end processing
18x (1.5 ... 4 mm²), 1x PE (1.5 ... 16 mm²)
— Connectable conductor cross-sections for
AWG cables, stranded
18x (18 ... 12)
Interfaces
Interfaces/bus type PROFIBUS DP
PROFIBUS DP
6BK1932-0AA00-0AA0 Subject to change without notice
Page 2/
4