Data Sheet
● Transmission rate, max.
12Mbit/s
● Design of electrical connection of PROFIBUS
interface
ECOFAST
Protocols
PROFIBUS DP Yes
Interrupts/diagnostics/status information
Number of status displays 2
LED status display LED green = status indicator, LED red = fault indicator
Diagnostics function Voltage diagnostics
Diagnostic messages
● Wire-break
Yes
● Fuse blown
Yes
● Load failure
Yes
Integrated Functions
Monitoring functions
● Temperature monitoring
Yes
● Type of temperature monitoring
NTC thermistor
Measuring functions
● Voltage measurement
Yes
Potential separation
Design of electrical isolation Optocoupler between main circuit and PELV
between the outputs No
Isolation
Overvoltage category III
Degree of pollution 2
EMC
EMC interference emission in accordance with IEC 61000-6-4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC 61000-4-3 10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ...
2.7 GHz)
Conducted interference due to burst acc. to IEC
61000-4-4
2 kV power supply lines / 1 kV signal lines
Conducted interference due to surge acc. to IEC
61000-4-5
On supply lines: 1 kV symmetrical, 2 kV asymmetrical, (24 V DC
supply only with external protective measure) for PROFIBUS
cable : asymmetrical 1 kV
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection IP65
Standards, approvals, certificates
6BK1932-0AA00-0AA0 Subject to change without notice
Page 3/
4
09/15/2019 © Copyright Siemens