Data Sheet

— Connectable conductor cross-sections for
AWG cables
1x (26 ... 12)
Power
Active power input 3W
Hardware configuration
Type of power output connectable POM4220
Slots
● Number of slots
1
Interfaces
Interfaces/bus type PROFINET IO
Supports protocol for PROFINET IO
● Transmission rate, max.
100Mbit/s
● Design of electrical connection of PROFINET
interface
2x RJ45
Protocols
Supports protocol for PROFINET IO Yes
PROFIBUS DP No
Further protocols
● EtherNet/IP
No
Interrupts/diagnostics/status information
Number of status displays 3
LED status display LED green = ready, LED yellow = heating on/off, LED red = error
display
Isolation
Overvoltage category III
Degree of pollution 2
EMC
EMC interference emission Limit value in accordance with IEC 61000-6-4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharging, 8 kV air discharging
Field-related interference acc. to IEC 61000-4-3 10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ...
2.7 GHz)
Conducted interference due to burst acc. to IEC
61000-4-4
2 kV power supply lines, 2 kV PROFINET cables
Conducted interference due to surge acc. to IEC
61000-4-5
DC supply lines: 0.5 kV symmetric and unsymmetric PROFINET
cables: 1 kV unsymmetric
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
6BK1942-1AA00-0AA0 Subject to change without notice
Page 2/
3
09/13/2019 © Copyright Siemens