Datasheet
Datasheet 6ED1052-2MD00-0BA8
Installation type/mounting
Mounting on 35 mm DIN rail, 4 spacing units wide
Supply voltage
12 V DC Yes
24 V DC Yes
permissible range, lower limit (DC) 10.8V
permissible range, upper limit (DC) 28.8V
Time of day
Time switching clocks
● Number
8
● Power reserve
480h
Digital inputs
Number of digital inputs 8; Of which 4 can be used in analog mode (0 to 10 V)
Digital outputs
Number of digital outputs 4; Relays
Short-circuit protection No; external fusing necessary
Output current
● for signal "1" permissible range for 0 to 55 °C,
max.
10A
Relay outputs
Switching capacity of contacts
— with inductive load, max.
3A
— with resistive load, max.
10A
EMC
Emission of radio interference acc. to EN 55 011
● Emission of radio interference acc. to EN 55
011 (limit class B)
Yes
6ED1052-2MD00-0BA8 Changes preserved