Brochure
Basic units LOGO! 12/24RC
1)
, LOGO! 12/24RCo
2)
LOGO! 24C, LOGO! 24Co LOGO! 24RC
1)
, LOGO! 24RCo
2)
LOGO! 230RC
1)
, LOGO! 230RCo
2)
LOGO! 12/24 RCE LOGO! 230 RCE
Inputs 8 8 8 8 8 8
of which can be used in analog mode
4 (0 to 10 V) 4 (0 to 10 V) – – 4 (0 to 10 V) –
Input/supply voltage 12/24 V DC 24 V DC 24 V AC/DC 115/240 V AC/DC 12/24 V DC 115/240 V AC/DC
Permissible range
with signal “0”
with signal “1”
Input current
10.8 V ... 28.8 V DC
max. 5 V DC
min. 8.5 V DC
1.5 mA (Ι3 ... Ι6), 0.1 mA (Ι 1, Ι 2, Ι 7, Ι 8)
20.4 V ... 28.8 V DC
max. 5 V DC
min. 12 V DC
2 mA (Ι3 ... Ι6), 0.1 mA (Ι 1, Ι 2, Ι 7, Ι 8)
20.4 ... 28.8 V DC
20.4 ... 26.4 V AC
max. 5 V AC/DC
min. 12 V AC/DC, 2.5 mA
85 ... 265 V AC
100 ... 253 V DC
max. 40 V AC/30 V DC
min. 79 V AC/79 V DC, 0.08 mA
10.8 V ... 28.8 V DC
max. 5 V DC
min. 8.5 V DC
1.5 mA (I3 ... I6) 0.1 mA (I 1, I 2, I 7, I 8)
85 ... 265 V AC
100 ... 253 V DC
max. 40 V AC/30 V DC
min. 79 V AC/79 V DC, 0.08 mA
Outputs 4 relays 4 transistors 4 relays 4 relays 4 relays 4 relays
Continuous current 10 A with resistive load;
3 A with inductive load
0.3 A 10 A with resistive load;
3 A with inductive load
10 A with resistive load;
3 A with inductive load
10 A with resistive load;
3 A with inductive load
10 A with resistive load;
3 A with inductive load
Short-circuit protection External fuse required Electronic (approx. 1 A) External fuse required External fuse required External fuse required External fuse required
Switching frequency 2 Hz with resistive load;
0.5 Hz with inductive load
10 Hz 2 Hz with resistive load;
0.5 Hz with inductive load
2 Hz with resistive load;
0.5 Hz with inductive load
2 Hz with resistive load;
0.5 Hz with inductive load
2 Hz with resistive load;
0.5 Hz with inductive load
Cycle time < 0.1 ms/function < 0.1 ms/function < 0.1 ms/function < 0.1 ms/function < 0.1 ms/function < 0.1 ms/function
Integrated time switches/
power reserve
Yes / typ. 80 h
(2 years with battery module)
Yes / typ. 80 h
(2 years with battery module)
Yes / typ. 80 h
(2 years with battery module)
Yes / typ. 80 h
(2 years with battery module)
Yes / typ. 480 h; no battery Yes / typ. 480 h; no battery
Connection cables 2 x 1.5 mm
2
or 1 x 2.5 mm
2
Ambient temperature 0 to + 55 ºC
Storage temperature – 40 ºC to + 70 ºC
Emitted interference In accordance with EN 55011 (limit class B)
Degree of protection IP20
Certification In accordance with VDE 0631, IEC 1131, FM Class 1, Div 2, cULus, C-Tick, marine approvals
Mounting On 35 mm standard mounting rail, 4 MW, or wall-mounting
On 35 mm standard mounting rail, 6 MW, or wall-mounting
Dimensions 72 (4 MW) x 90 x 55 mm (W x H x D) 108 (6 MW) x 90 x 55 mm (W x H x D) 108 (6 MW) x 90 x 55 mm (W x H x D)
Programming cable LOGO! PC cable, (RS232 or USB) LOGO! PC cable, (RS232 or USB) LOGO! PC cable, (RS232 or USB) LOGO! PC cable, (RS232 or USB) Ethernet Ethernet
Optional backup battery Yes Yes Yes Yes No No
LOGO! <=> LOGO!
communication (Ethernet)
No No No No Yes, max. 8 LOGO!s + 1PC/PG Yes, max. 8 LOGO!s + 1PC/PG
LOGO! <=> network
(Ethernet)
No No No No Yes, max. 8 TN
(LOGO!, SIMATIC CPU, 1x SIMATIC HMI, PC)
Yes, max. 8 TN
(LOGO!, SIMATIC CPU, 1x SIMATIC HMI, PC)
Maximum
program memory
200 blocks 200 blocks 200 blocks 200 blocks 400 blocks 400 blocks
External memory module LOGO! memory card LOGO! memory card LOGO! memory card LOGO! memory card SIMATIC memory card or
standard SD card max. 8 GB
SIMATIC memory card or
standard SD card max. 8 GB
Data logging No No No No Internal memory/SD card Internal memory/SD card
Online status chart No No No No Yes, with saving on the PC Yes, with saving on the PC
Macro function No No No No Yes Yes
Digital modules LOGO! DM8 12/24R LOGO! DM8 24
DM16 24
LOGO! DM8 24R
DM16 24R
LOGO! DM8 230R
DM16 230R
Inputs 4 4/8 4/8 4/8
Input/supply voltage 12/24 V DC 24 V DC 24 V AC/DC*
24 V DC**
115/240 V AC/DC
Permitted range 10.8 ... 28.8 V DC 20.4 ... 28.8 V DC 20.4 ... 28.8 V DC, 20.4 ... 26.4 V AC* 85 ... 265 V AC, 100 ... 253 V DC
with signal “0”
with signal “1”
max. 5 V DC
min. 8.5 V DC
max. 5 V DC
min. 12 V DC
max. 5 V AC/DC
min. 12 V AC/DC*
max. 40 V AC
min. 79 V AC
Input current 1.5 mA 2 mA 2.5 mA*, 2.0 mA** 0.08 mA
Outputs 4 relays 4/8 transistors 4/8 relays 4/8 relays
Continuous current Ith (per terminal) 5 A with resistive load;
3 A with inductive load
0.3 A 5 A with resistive load;
3 A with inductive load
5 A with resistive load;
3 A with inductive load
Short-circuit protection External fuse required Electronic (approx. 1 A) External fuse required External fuse required
Switching frequency 2 Hz with resistive load;
0.5 Hz with inductive load
10 Hz 2 Hz with resistive load;
0.5 Hz with inductive load
2 Hz with resistive load;
0.5 Hz with inductive load
Power loss 0.3 ... 1.7 W at 12 V DC
0.4 ... 1.8 W at 24 V DC
0.8 ... 1.1 W*
0.8 ... 1.7 W**
0.4 ... 1.8 W at 24 V DC*
0.9 ... 2.7 W at 24 V AC*
0.7 ... 2.5 W at 24 V DC**
1.1 ... 3.5 W (115 V AC) ... 4.5**
2.4 ... 4.8 W (240 V AC) ... 5.5**
0.5 ... 1.8 W (115 V DC) ... 2.9**
1.2 ... 2.4 W (240 V DC) ... 4.8**
Dimensions (W x H x D) 36 (2 MW) x 90 x 53 mm 36 (2 MW) x 90 x 53 mm
72 (4 MW) x 90 x 53 mm
36 (2 MW) x 90 x 53 mm
72 (4 MW) x 90 x 53 mm
36 (2 MW) x 90 x 53 mm
72 (4 MW) x 90 x 53 mm
LOGO! modular – the technical details