User Manual

LOGO! functions
4.4 Special functions list - SF
LOGO!
166 Manual, 04/2011, A5E03556174-01
4.4.3 On-/Off-delay
Short description
The on-/off-delay function sets the output after the set on-delay time has expired, and resets
it upon expiration of the off-delay time.
Symbol in LOGO! Wiring Description
Input Trg A positive edge (0 to 1 transition) at input Trg
(Trigger) triggers the on-delay time T
H
.
A negative edge (1 to 0 transition) at input Trg
(Trigger) triggers the off-delay time T
L
.
Parameter T
H
is the time after which the output is set hi (output
signal transition 0 to 1).
T
L
is the time after which the output is reset ( output
signal transition 1 to 0).
Retentivity:
/ = No retentivity
R = The status is retentive.
4
7UJ
3DU
Output Q Q is set when the configured time T
H
has expired and
Trg is still set. It is reset on expiration of the time T
L
, if
the trigger Trg has not been set again.
Parameters T
H
and T
L
Note the preset values for the parameters T
H
and T
L
in topic Time response (Page 151).
The on-delay and off-delay times for parameters T
H
and T
L
can be based on the actual value
of another, already-configured function. You can use the actual values of the following
functions:
Analog comparator (Page 218) (actual value Ax - Ay)
Analog threshold trigger (Page 213) (actual value Ax)
Analog amplifier (Page 226) (actual value Ax)
Analog multiplexer (Page 248) (actual value AQ)
Analog ramp (Page 251) (actual value AQ)
Mathematic instruction (Page 265) (actual value AQ)
PI controller (Page 256) (actual value AQ)
Up/down counter (Page 201) (actual value Cnt)
If your LOGO! is a LOGO!
0
BA7, you can additionally use the actual values of the following
functions:
Analog filter (0BA7 only) (Page 271) (actual value AQ)
Average value (0BA7 only) (Page 276) (actual value AQ)
Max/Min (0BA7 only) (Page 273) (actual value AQ)