LOGO! functions
4.4 Special functions list - SF
LOGO!
262 Manual, 04/2011, A5E03556174-01
If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following
functions:
● Analog filter (0BA7 only) (Page 271) (actual value AQ)
● Average value (0BA7 only) (Page 276) (actual value AQ)
● Max/Min (0BA7 only) (Page 273) (actual value AQ)
● On-delay (Page 160) (current time Ta)
● Off-delay (Page 164) (current time Ta)
● On-/Off-delay (Page 166) (current time Ta)
● Retentive on-delay (Page 168) (current time Ta)
● Wiping relay (pulse output) (Page 170) (current time Ta)
● Edge triggered wiping relay (Page 172) (current time Ta)
● Asynchronous pulse generator (Page 175) (current time Ta)
● Stairway lighting switch (Page 179) (current time Ta)
● Multiple function switch (Page 182) (current time Ta)
● Stopwatch (0BA7 only) (Page 198) (actual value AQ)
● Threshold trigger (Page 210) (actual value Fre)
Select the re
quire
d function by the block number. The timebase is configurable. For
information on valid ranges and parameter defaults, refer to the On-delay (Page 160) topic.
Parameters p (number of decimals)
Parameter p applies only to the display of the Ax value in a message text
Functional description
The function reads the value of the signal at the analog input Ax.
This value is multiplied by the value of parameter A (gain). Parameter B (offset) is added to
the product, as follows:
(Ax • Gain) + Offset = Actual value Ax
The function block calculates the proportion of the actual value Ax to the range. The block
sets the digital output Q high for the same proportion of the T (periodic time) parameter, and
sets Q low for the remainder of the time period.