4.4.5 Wiping relay (pulse output)
Short description
An input signal generates a signal with a configurable period at the output.
Symbol in LOGO! Wiring Description
Input Trg A signal at input Trg (Trigger) triggers the time for the
wiping relay function.
Parameter The output is switched off after the time T has expired
(output signal transition 1 to 0).
Retentivity:
/ = No retentivity
R = The status is retentive.
4
7UJ
3DU
Output Q A signal at input Trg sets Q. If the input signal = 1,
output Q remains set for the time Ta.
Parameter T
Note the information on parameter T in topic Time response (Page 151).
The time for parameter T can be provided by the actual value of another already-
programmed function. You can use the actual values of the following functions:
Analog comparator (Page 218) (actual value Ax – Ay)
Analog threshold trigger (Page 213) (actual value Ax)
Analog amplifier (Page 226) (actual value Ax)
Analog multiplexer (Page 248) (actual value AQ)
Analog ramp (Page 251) (actual value AQ)
Mathematic instruction (Page 265) (actual value AQ)
PI controller (Page 256) (actual value AQ)
Up/down counter (Page 201) (actual value Cnt)
If your LOGO! is a LOGO!
0
BA7, you can additionally use the actual values of the following
functions:
Analog filter (0BA7 only) (Page 271) (actual value AQ)
Average value (0BA7 only) (Page 276) (actual value AQ)
Max/Min (0BA7 only) (Page 273) (actual value AQ)
On-delay (Page 160) (current time Ta)
Off-delay (Page 164) (current time Ta)
On-/off-delay (Page 166) (current time Ta)
Retentive on-delay (Page 168) (current time Ta)