Datasheet

Rated voltage Vout DC 24V
Total tolerance, static ± 2%
Static mains compensation, approx. 0.5%
Static load balancing, approx. 1%
Residual ripple peak-peak, max. 100mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 100mV
Adjustment range 22...28V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
On/off behavior Overshoot of Vout < 2 %
Startup delay, max. 1s
Voltage increase time of the output voltage maximum 30ms
Rated current value Iout rated 2.1A
Current range 0...2.1A
● Note
+50 ... +70 °C: Derating 2.5%/K
Supplied active power typical 50W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 86%
Power loss at Vout rated, Iout rated, approx. 8W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.5%
Dynamic load smoothing (Iout: 50/100/50 %), Uout ±
typ.
5%
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 2.5A
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current RMS value
● typical
6A
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra low output voltage Vout according to EN 60950-1
Protection class Class I
Leakage current
● maximum
3.5mA
6EP1331-1LD00 Subject to change without notice
Page 2/
3
07/31/2018 © Copyright Siemens