Datasheet

● typical
1mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus (UL 60950-1, CSA C22.2 No. 60950-1), File E151273
Explosion protection -
FM approval -
CB approval Yes
Marine approval -
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation
-10...+70°C
— Note
with natural convection
● during transport
-40...+85°C
● during storage
-40...+85°C
Mechanics
Connection technology screw-type terminals
Connections
● Supply input
L, N, PE: 1 screw terminal each for 0.3 ... 1.3 mm² single-
core/finely stranded
● Output
+, -: 1 screw terminal each for 0.3 ... 1.3 mm²
● Auxiliary
-
Width of the enclosure 97mm
Height of the enclosure 128mm
Depth of the enclosure 38mm
Required spacing
● top
20mm
● bottom
0mm
● left
20mm
● right
20mm
Weight, approx. 0.37kg
Installation Wall mounting
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6EP1332-1LD00 Subject to change without notice
Page 3/
3
07/31/2018 © Copyright Siemens