Datasheet

I²t, max. 3.3 A²·s
Built-in incoming fuse T 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 10 A characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.5 %
Residual ripple peak-peak, max. 150 mV
Residual ripple peak-peak, typ. 50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 240 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 150 mV
Adjustment range 22.8 … 26.4 V
Product feature / output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for 24 V OK
On/off behavior Overshoot of Vout approx. 4 %
Startup delay, max. 1.5 s
Voltage rise, typ. 170 ms
Rated current value Iout rated 10 A
Current range 0 … 10 A
• Note +45 ... +60 °C: Derating 2%/K
delivered active power / typ. 240 W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 89 %
Power loss at Vout rated, Iout rated, approx. 34 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.3 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ. 2 %
Load step setting time 10 to 90%, typ. 0.5 ms
Load step setting time 90 to 10%, typ. 0.7 ms
Protection and monitoring
Output overvoltage protection < 33 V
Current limitation, typ. 10.5 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Constant current characteristic
6EP1334-1LB00
Page 2/ 05/19/2014
subject to modifications
© Copyright Siemens AG 2014