Datasheet

Stabilized Power Supplies
SITOP 6EP Power Supplies
SITOP smart,
single-phase and three-phase
11/57
Siemens IC 10 · 2011
* You can order this quantity or a multiple thereof.
Illustrations are approximate
11
Overview
Small in size, big in performance. SITOP smart requires little
room on the standard mounting rail and offers high functionality
at an attractive price. With its good-natured overload behavior,
even loads with a high inrush current can be smoothly switched
on. If required, 50 % extra power can be supplied for a duration
of 5 s. In addition, the 24 V versions will permanently supply
120 % of the rated power provided the ambient temperature
does not exceed 45 °C.
For 24 V standard applications of 2.5 A to 20 A and for 48 V
standard applications of 10 A
Compact design for small mounting area, no lateral clearance
required
Easy standard rail mounting
Smooth switching on of loads with high inrush current such as
DC/DC transformers and motors
More performance thanks to permanent 120 % of rated power
up to an ambient temperature of 45 °C (24 V versions)
Large setting range for the output voltage, using potentiome-
ters which are easy to reach from the front
Parallel switching option to increase performance
Extensive certifications according to UL, CSA, GL
(Germanischer Lloyd) and ATEX directives (Atmosphère
Explosible)
For universal use – in industry and public low-voltage systems
– worldwide
Can be combined with SITOP expansion modules and the
uninterruptible power supplies (24 V versions)
Selection and ordering data
For other units and versions, see Catalog KT 10.1.
Version Inputs Output Dimensions
(W x H x D)
DT Order No. Price
per PU
PU
(UNIT,
SET, M)
PS* PG
Rated
voltage
U
e Rated
Rated
voltage
U
a Rated
Rated
current
I
a Rated
mm
6EP1 332-2BA10
6EP1 333-2.A10
6EP1 334-2.A01
6EP1 436-2BA10
6EP1 456-2BA00
Power supplies 24 V
Limitation of input current harmonics according to EN 61000-3-2
2.5 A 120/230 V AC
(85 ... 132 V/
170 ... 264 V)
24 V DC
±3 %
2 A 32.5 x 125 x
125
} 6EP1 332-2BA10 1 1 unit 582
Limitation of input current harmonics according to EN 61000-3-2
5 A 120/230 V AC
(85 ... 132 V/
170 ... 264 V)
24 V DC
±3 %
5 A 50 x 125 x 125 } 6EP1 333-2BA01 1 1 unit 582
5 A 120/230 V AC
(85 ... 132 V/
170 ... 264 V)
24 V DC
±3 %
5 A 50 x 125 x 125 }
6EP1 333-2AA01 1 1 unit 582
Limitation of input current harmonics according to EN 61000-3-2
10 A 120/230 V AC
(85 ... 132 V/
170 ... 264 V)
24 V DC
±3 %
10 A 70 x 125 x 125 } 6EP1 334-2BA01 1 1 unit 582
10 A 120/230 V AC
(85 ... 132 V/
170 ... 264 V)
24 V DC
±3 %
10 A 70 x 125 x 125 }
6EP1 334-2AA01 1 1 unit 582
20 A 3 AC 400 ... 500 V
(340 ... 550 V)
24 V DC
±3 %
20 A 90 x 145 x 150 }
6EP1 436-2BA10 1 1 unit 582
Power supplies 48 V
Limitation of input current harmonics according to EN 61000-3-2
10 A 3 AC 400 ... 500 V
(360 ... 550 V)
48 V DC
±3 %
10 A 70 x 125 x 125 A 6EP1 456-2BA00 1 1 unit 582
IC10_11.book Seite 57 Donnerstag, 16. Dezember 2010 7:53 07
© Siemens AG 2010

Summary of content (4 pages)