Datasheet

6EP3321-7SB00-0AX0
SITOPPSU620012V/2A
support.industry.siemens.com|ProductSupport|Friday,11.January2019
Printthispage GeneratePDF
Technicaldata
SITOPPSU620012V/2A
SITOPPSU620012V/2AStabilizedpowersupplyInput:120-230VAC,(120-240VDC)
Output:12VDC/2A
Input
Input 1-phaseACorDC
RatedvoltagevalueVinrated 120...230V
VoltagerangeAC 85...264V
Supplyvoltage
●atDC 120...240V
Inputvoltage
●atDC 110...275V
Wide-rangeinput Yes
MainsbufferingatIoutrated,min. 150ms;atVin=230V
Ratedlinefrequency1 50Hz
Ratedlinefrequency2 60Hz
Ratedlinerange 47...63Hz
Inputcurrent
●atratedinputvoltage120V 0.45A
●atratedinputvoltage230V 0.25A
Switch-oncurrentlimiting(+25°C),max. 32A
Built-inincomingfuse 3.15A
Output
Output Controlled,isolatedDCvoltage
Numberofoutputs 1
RatedvoltageVoutDC 12V
Totaltolerance,static± 3%
Staticmainscompensation,approx. 0.3%
Staticloadbalancing,approx. 0.3%
Residualripplepeak-peak,max. 30mV
Residualripplepeak-peak,typ. 20mV
Spikespeak-peak,max.(bandwidth:20MHz) 20mV
Spikespeak-peak,typ.(bandwidth:20MHz) 10mV
Adjustmentrange 10.5...12.9V
ProductfunctionOutputvoltageadjustable Yes
Outputvoltagesetting viapotentiometer;max.24W
Statusdisplay GreenLEDfor24VOK
On/offbehavior OvershootofVoutapprox.3%
Startupdelay,max. 1s
Voltagerise,typ. 50ms
RatedcurrentvalueIoutrated 2A
Currentrange 0...2A
●Note +60...+70°C:Derating2%/K
Suppliedactivepowertypical 24W
Short-termoverloadcurrent
●onshort-circuitingduringthestart-uptypical 2A
●atshort-circuitduringoperationtypical 2A
Efficiency
EfficiencyatVoutrated,Ioutrated,approx. 83.3%
PowerlossatVoutrated,Ioutrated,approx. 5W
Powerloss[W]duringno-loadoperationmaximum 0.8W
Closed-loopcontrol
Dynamicloadsmoothing(Iout:10/90/10%),Uout±typ. 4%
Loadstepsettingtime10to90%,typ. 2ms
Loadstepsettingtime90to10%,typ. 2ms
Settingtimemaximum 3ms
Protectionandmonitoring
Outputovervoltageprotection <20V
Currentlimitation,typ. 2.8A
PropertyoftheoutputShort-circuitproof Yes
Short-circuitprotection Shutdownandperiodicrestartattempts
Safety
Primary/secondaryisolation Yes
Galvanicisolation SafetyextralowoutputvoltageVoutaccordingtoEN60950-1
Protectionclass ClassI
Leakagecurrent
●maximum 3.5mA
CEmark Yes
UL/cUL(CSA)approval cULus-Listed(UL508,CSAC22.2No.107.1),FileE197259;cCSAus(CSAC22.2No.

Summary of content (2 pages)