Datasheet

Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 10 A characteristic
B or from 6 A characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 12V
Total tolerance, static ± 3%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 0.1%
Residual ripple peak-peak, max. 200mV
Residual ripple peak-peak, typ. 30mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 300mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 50mV
Adjustment range 10.5...16.1V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for output voltage OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 0.5s
Voltage rise, typ. 100ms
Rated current value Iout rated 4.5A
Current range 0...4.5A
● Note
+55 ... +70 °C: Derating 2%/K
Supplied active power typical 54W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 87.1%
Power loss at Vout rated, Iout rated, approx. 8W
Power loss [W] during no-load operation maximum 0.3W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.2%
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
4%
Load step setting time 10 to 90%, typ. 1ms
Load step setting time 90 to 10%, typ. 1ms
Protection and monitoring
Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 5A
Property of the output Short-circuit proof Yes
Short-circuit protection Constant current characteristic
6EP3322-6SB00-0AY0 Subject to change without notice
Page 2/
4
04/13/2018 © Copyright Siemens