Datasheet
Enduring short circuit current RMS value
● maximum
5A
Overcurrent overload capability in normal operation overload capability 150% Iout rated typ. 200 ms
Overload/short-circuit indicator -
measuring point for output current 50 mV =^ 4.5 A
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class II (without protective conductor)
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File
E151273, NEC class 2 (acc. to UL 1310)
Explosion protection ATEX (EX) II 3G Ex nA IIC T3; cULus Class I Div. 2 (ANSI/ISA-
12.12.01, CSA C22.2 No. 213) Group ABCD, T4, File E488866
FM approval Class I, Div. 2, Group ABCD, T4
CB approval Yes
Marine approval ABS, DNV GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation
-25...+70°C
— Note
with natural convection
● during transport
-40...+85°C
● during storage
-40...+85°C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input
L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely
stranded
● Output
+, -: 1 screw terminal each for 0.5 ... 2.5 mm²
● Auxiliary
-
Width of the enclosure 54mm
Height of the enclosure 90mm
Depth of the enclosure 53mm
Required spacing
6EP3322-6SB00-0AY0 Subject to change without notice