Data Sheet

— up to 50 °C, max.
4.7A; DQ mode
— up to 60 °C, max.
2.5A; DQ mode
vertical installation
— up to 30 °C, max.
7.2A; DQ mode
— up to 40 °C, max.
5.6A; DQ mode
— up to 50 °C, max.
4A; DQ mode
Cable length
● shielded, max.
50m
● unshielded, max.
50m
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes; Operating modes DQ and OVS only
Execution and activation time (TCO), min. 40µs
Bus cycle time (TDP), min. 125µs
Jitter, max. 1µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Diagnostic information readable
Yes
● Monitoring the supply voltage
Yes
● Wire-break
No
● Short-circuit
Yes; Module-wise
● Group error
Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green PWR LED
● Channel status display
Yes; Green LED
● for channel diagnostics
No
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
6ES7132-6BD20-0DA0 Subject to change without notice