Data Sheet
● PWM
No
● Oversampling
No
● MSO
No
Redundancy
● Redundancy capability
Yes
Supply voltage
Rated value (DC) 24V
permissible range, lower limit (DC) 19.2V
permissible range, upper limit (DC) 28.8V
Reverse polarity protection Yes
Input current
Current consumption, max. 60mA; without load
Output voltage
Rated value (DC) 24V
Power loss
Power loss, typ. 1W
Address area
Address space per module
● Address space per module, max.
2byte
Hardware configuration
Automatic encoding
● Mechanical coding element
Yes
Selection of BaseUnit for connection variants
● 1-wire connection
BU type A0
● 2-wire connection
BU type A0 + Potential isolation module
● 3-wire connection
BU type A0 + Potential isolation module
● 4-wire connection
BU type A0 + Potential isolation module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection Yes
● Response threshold, typ.
0.7 to 1.3 A
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max.
0.5A
● on lamp load, max.
5W
6ES7132-6BH00-0BA0 Subject to change without notice
Page 2/
5
09/16/2019 © Copyright Siemens