Data Sheet

● PWM
No
● Oversampling
No
● MSO
No
Redundancy
● Redundancy capability
Yes
Supply voltage
Rated value (DC) 24V
permissible range, lower limit (DC) 19.2V
permissible range, upper limit (DC) 28.8V
Reverse polarity protection Yes
Input current
Current consumption, max. 60mA; without load
Output voltage
Rated value (DC) 24V
Power loss
Power loss, typ. 1W
Address area
Address space per module
● Address space per module, max.
2byte
Hardware configuration
Automatic encoding
● Mechanical coding element
Yes
Selection of BaseUnit for connection variants
● 1-wire connection
BU type A0
● 2-wire connection
BU type A0 + Potential isolation module
● 3-wire connection
BU type A0 + Potential isolation module
● 4-wire connection
BU type A0 + Potential isolation module
Digital outputs
Type of digital output Source output (PNP, current-sourcing)
Number of digital outputs 16
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection Yes
● Response threshold, typ.
0.7 to 1.3 A
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max.
0.5A
● on lamp load, max.
5W
6ES7132-6BH00-0BA0 Subject to change without notice
Page 2/
5
09/16/2019 © Copyright Siemens