Data Sheet

Operational error limit in overall temperature range
● Current, relative to input range, (+/-)
0.3%
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-)
0.2%
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt
Yes
Diagnostic messages
● Diagnostic information readable
Yes
● Wire-break
Yes; Measuring range 4 to 20 mA only
● Group error
Yes
● Overflow/underflow
Yes
Diagnostics indication LED
● Group error SF (red)
Yes
Parameter
Diagnostics wire break At 4 to 20 mA
Measurement type/range 4 to 20 mA, 0 to 20 mA, ±20 mA
Group diagnostics Yes
Overflow/underflow Yes
Potential separation
Potential separation analog inputs
● between the channels
No
● between the channels and backplane bus
Yes
● Between the channels and load voltage L+
Yes
Permissible potential difference
between MANA and M internally (UISO) 75 V DC/60 V AC
Dimensions
Width 15mm
Height 81mm
Depth 52mm
Weights
Weight, approx. 45g
last modified:
09/11/2019
6ES7134-4GB62-0AB0 Subject to change without notice
Page 3/
3
09/13/2019 © Copyright Siemens