Data Sheet

● MSI
No
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24V
permissible range, lower limit (DC) 19.2V
permissible range, upper limit (DC) 28.8V
Reverse polarity protection Yes
Input current
Current consumption, max. 25mA
Power loss
Power loss, typ. 0.7W
Address area
Address space per module
● Address space per module, max.
16byte
Hardware configuration
Selection of BaseUnit for connection variants
● 1-wire connection
BU type A0, A1
● 2-wire connection
BU type A0, A1
Analog inputs
Number of analog inputs 8; Single-ended
● For voltage measurement
8
permissible input voltage for voltage input
(destruction limit), max.
30V
Cycle time (all channels), min. 1ms; per channel
Input ranges (rated values), voltages
● 0 to +10 V
Yes; 15 bit
● Input resistance (0 to 10 V)
100kΩ
● -10 V to +10 V
Yes; 16 bit incl. sign
● Input resistance (-10 V to +10 V)
100kΩ
Cable length
● shielded, max.
200m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
● Integration time, parameterizable
Yes
● Interference voltage suppression for
interference frequency f1 in Hz
16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60)
6ES7134-6FF00-0AA1 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens