Data Sheet

● MSI
No
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24V
permissible range, lower limit (DC) 19.2V
permissible range, upper limit (DC) 28.8V
Reverse polarity protection Yes
Input current
Current consumption, max. 25mA
Power loss
Power loss, typ. 0.7W
Address area
Address space per module
● Address space per module, max.
16byte
Hardware configuration
Selection of BaseUnit for connection variants
● 1-wire connection
BU type A0, A1
● 2-wire connection
BU type A0, A1
Analog inputs
Number of analog inputs 8; Single-ended
● For voltage measurement
8
permissible input voltage for voltage input
(destruction limit), max.
30V
Cycle time (all channels), min. 1ms; per channel
Input ranges (rated values), voltages
● 0 to +10 V
Yes; 15 bit
● Input resistance (0 to 10 V)
100kΩ
● -10 V to +10 V
Yes; 16 bit incl. sign
● Input resistance (-10 V to +10 V)
100kΩ
Cable length
● shielded, max.
200m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
● Integration time, parameterizable
Yes
● Interference voltage suppression for
interference frequency f1 in Hz
16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60)
6ES7134-6FF00-0AA1 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens