Data Sheet

● Conversion time (per channel)
180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms
Smoothing of measured values
● Number of smoothing levels
4; None; 4/8/16 times
● parameterizable
Yes
Encoder
Connection of signal encoders
● for voltage measurement
Yes
● for current measurement as 4-wire transducer
No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01%
Temperature error (relative to input range), (+/-) 0.005%/K
Crosstalk between the inputs, min. -50dB
Repeat accuracy in steady state at 25 °C (relative to
input range), (+/-)
0.05%
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-)
0.5%
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-)
0.3%
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of
interference < rated value of input range), min.
70dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
No
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm
Yes
● Limit value alarm
No
Diagnostic messages
● Monitoring the supply voltage
Yes
● Wire-break
No
● Short-circuit
No
● Group error
Yes
● Overflow/underflow
Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green PWR LED
● Channel status display
Yes; Green LED
● for channel diagnostics
No
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
6ES7134-6FF00-0AA1 Subject to change without notice