Brochure

SIMATIC ET 200iSP 37
SIMATIC ET 200iSP
The intrinsically-safe version for hazardous areas
ET 200S with redundant PROFIBUS connection
ET 200iSP can be used in hazardous areas with a gas or
dust atmosphere:
The ET 200iSP station can be installed in Zones 1, 21 and 2,
22.
The connected sensors and actuators can also be located in
Zones 0 and 20.
Communication between the field devices and the process
control system or automation system is performed over
PROFIBUS DP. This considerably reduces the wiring outlay. The
terminal blocks commonly used today, as well as the neces-
sary distribution boards and Ex isolating transformers for the
signals, can be omitted.
PROFIBUS DP has established itself as the standard bus in the
field level right up to hazardous areas. This open and system-
wide communication keeps the solution flexible and also
open to other manufacturers. International standardization of
PROFIBUS DP also ensures future protection to the customer
for investments that are often considerable and intended to
last for many years.
ET 200iSP supports high availability of the system thanks to:
Configuration during normal operation
Hot swapping
Redundancy
During normal operation
stations can be added,
stations can be expanded with modules, and
module parameters changed.
The independent wiring supports easy, reliable replacement
of modules during normal operation. Hot swapping of the
power supply is possible without arcing. PROFIBUS DP and/or
the power supply can also be redundantly implemented.
HART support
ET 200iSP offers the HART protocol for connecting process de-
vices with HART capability. These HART modules also support
the transfer of auxiliary variables. Apart from the actual mea-
sured value, up to four IEEE variables can be transferred in the
process image. By means of a routing function, a central sta-
tion can access the HART process devices transparently over
PROFIBUS DP. A higher-level control system can therefore per-
form central data administration. The process devices are con-
nected by means of a 4 to 20 mA analog signal. Further device
information is transferred over a modulated signal:
Parameters that are specified by a central engineering
station (routing)
Diagnostics data that are read by the engineering station
This principle is called HART (Highway Addressable Remote
Transducer). The majority of process instruments, e.g. for
temperature, level, pressure or flow measurements, have
HART connections.
Powerful diagnostics with SIMATIC PCS 7
With SIMATIC ET 200iSP, numerous items of diagnostics infor-
mation are generated when internal and external faults occur,
e.g. on open-circuit or short-circuit.
The HART status of the connected HART field devices such as
maintenance and additional information is mirrored in the di-
agnostics and signaled to the host control system. Standard
diagnostics drivers are available for SIMATIC PCS 7 for the di-
agnostics messages. These drivers prepare all the relevant sig-
nals for the higher-level PCS 7 Operator System. The detected
faults are transferred quickly to the higher-level systems and
support online diagnostics from a central point at any time.
A watchdog module monitors the ET 200iSP by means of
targeted reading or writing of I/O data
Reading an input that switches (toggles) with a constant
frequency
Provision of an intrinsically safe power supply for the deac-
tivation signal of the digital outputs
SIMATIC_ET200_ENGLISCH.book Seite 37 Montag, 26. November 2012 10:02 10
© Siemens AG 2012