Data Sheet
● unshielded, max.
500m
Interrupts/diagnostics/status information
Diagnostics function Yes, "Alarms/diagnostic messages" section in the manual
Substitute values connectable No
Alarms
● Diagnostic alarm
Yes
Diagnostics indication LED
● RUN LED
Yes; Green LED
● ERROR LED
Yes; Red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green PWR LED
● Channel status display
Yes; Green LED
● for channel diagnostics
Yes; Red LED
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
● between the channels and the power supply of
the electronics
No
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions Yes
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1
PLe
● SIL acc. to IEC 61508
SIL 3
Probability of failure (for service life of 20 years and repair time of 100 hours)
— Low demand mode: PFDavg in
accordance with SIL3
< 2.00E-05
— High demand/continuous mode: PFH in
accordance with SIL3
< 1.00E-09 1/h
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
0°C
● horizontal installation, max.
60°C
● vertical installation, min.
0°C
● vertical installation, max.
50°C
Dimensions
Width 15mm
Height 73mm
6ES7136-6DB00-0CA0 Subject to change without notice
Page 3/
4
09/13/2019 © Copyright Siemens