Data Sheet

● between the channels, in groups of
4; DIQ channels are isolated from DQ channels
● between the channels and backplane bus
Yes
● between the channels and the power supply of
the electronics
No; DIQ channels are non-isolated and DQ channels are isolated
from supply voltage 1L+
Isolation
Isolation tested with 707 V DC (type test)
Degree and class of protection
IP degree of protection IP65/67
Standards, approvals, certificates
Suitable for safety-related tripping of standard
modules
Yes; From FS01
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1
PL d
● Category according to ISO 13849-1
Cat. 3
● SILCL according to IEC 62061
SILCL 2
Ambient conditions
Ambient temperature during operation
● min.
-25°C
● max.
55°C
Connection method
Design of electrical connection for the inputs and
outputs
M12, 5-pole
Design of electrical connection for supply voltage M8, 4-pole
ET-Connection
● ET-Connection
M8, 4-pin, shielded
Dimensions
Width 30mm
Height 159mm
Depth 40mm
Weights
Weight, approx. 145g
last modified:
09/12/2019
6ES7143-5AF00-0BA0 Subject to change without notice
Page 4/
4