Data Sheet

● Common mode interference (USS < 2.5 V) ,
min.
80dB; Interference voltage < 10 V
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm
Yes; Parameterizable
● Hardware interrupt
Yes; (limit value alarm), can be parameterized for channel 0
Diagnostic messages
● Diagnostic information readable
Yes
● Wire-break
Yes; at 1 to 5 V
● Short-circuit
Yes; at 1 to 5 V
Diagnostics indication LED
● Group error SF (red)
Yes
Potential separation
Potential separation analog inputs
● between the channels
No
● between the channels and backplane bus
Yes
Permissible potential difference
Between the inputs and MANA (UCM) 10 Vpp AC
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 45mm
Height 130mm
Depth 35mm
Weights
Weight, approx. 150g
last modified:
09/12/2019
6ES7144-4FF01-0AB0 Subject to change without notice
Page 3/
3
09/16/2019 © Copyright Siemens