Data Sheet

Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 30mA
Current output, no-load voltage, max. 20V
Output ranges, voltage
● 0 to 10 V
Yes
● 1 V to 5 V
Yes
● -10 V to +10 V
Yes
Output ranges, current
● 0 to 20 mA
Yes
● -20 mA to +20 mA
Yes
● 4 mA to 20 mA
Yes
Connection of actuators
● for voltage output two-wire connection
Yes
● for current output two-wire connection
Yes
Load impedance (in rated range of output)
● with voltage outputs, min.
1kΩ
● with voltage outputs, capacitive load, max.
1µF
● with current outputs, max.
600Ω
● with current outputs, inductive load, max.
1mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA
28.8 V permanent, 35 V for max. 500 ms
Cable length
● shielded, max.
30m
Analog value generation for the outputs
Analog value display SIMATIC S7 format
Conversion principle Resistor network
Integration and conversion time/resolution per channel
● Resolution (incl. overrange)
15 bit + sign
● Conversion time (per channel)
1ms
Settling time
● for resistive load
2ms
● for capacitive load
1.8ms
● for inductive load
2ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to
50 kHz), (+/-)
U: ±0.6 mVrms; I: ±0.4 nArms
Linearity error (relative to output range), (+/-) 0.02%
Temperature error (relative to output range), (+/-) U: 0.001%/°C; I: 0.0025%/°C
Crosstalk between the outputs, min. 70dB
Repeat accuracy in steady state at 25 °C (relative to
output range), (+/-)
0.008%
6ES7145-6HD00-0AB0 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens