Data Sheet
For process terminals, max. 5A
Hardware configuration
Automatic encoding Yes
Potential separation
between backplane bus and supply voltage Yes
between process terminals and supply voltage Yes
between power bus and supply voltage No
Isolation
Isolation tested with 3 100 V DC
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-30°C
● horizontal installation, max.
60°C
● vertical installation, min.
-30°C
● vertical installation, max.
50°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
2000m; On request: Installation altitudes greater than 2 000 m
Accessories
Color coding labels
● for AUX terminals
CC81 to CC83
Connection method
Terminals
● Terminal type
Push-in terminal
● Conductor cross-section, min.
0.14mm²; AWG 26
● Conductor cross-section, max.
2.5mm²; AWG 14
● Number of process terminals to I/O module
12; Pro slot
● Number of terminals to AUX bus
0
● Number of add-on terminals
0
● Number of terminals with connection to P1 and
P2 bus
0; Pro slot
Dimensions
Width 20mm
Height 117mm
Depth 35mm
Weights
Weight, approx. 48g
last modified:
09/11/2019
6ES7193-6BP20-2BB0 Subject to change without notice
Page 2/
2
09/16/2019 © Copyright Siemens