Exchanging a V3.0 CPU for a V4.0 CPU
B.1 Exchanging a V3.0 CPU for a V4.0 CPU
Easy Book
348 Manual, 03/2014, A5E02486774-AF
HMI panel communication
If you had one or more HMI panels (Page 22) connected to your S7-1200 V3.0 CPU, the
communication to the S7-1200 V4.0 CPU depends on the type of communication you use
and the firmware version of the HMI panel. Recompile and download your project to the CPU
and the HMI and/or update your HMI firmware.
Requirement to recompile program blocks
After exchanging a V3.0 CPU for a V4.0 CPU, you must recompile all program blocks before
you can download them to the V4.0 CPU. Additionally, if any of the blocks have know-how
protection (Page 84) or copy protection bound to a PLC serial number (Page 85), you must
remove the protection before you compile and download the blocks. (You do not, however,
need to deactivate copy protection bound to a memory card.) After the download, you can
reconfigure the know-how protection and/or PLC serial number copy protection. Note that if
your project includes any blocks with know-how protection that an OEM (Original Equipment
Manufacturer) provided, you must contact the OEM to provide V4.0 versions of those blocks.
In general, Siemens recommends that you recompile the hardware configuration and
software in STEP 7 and download to all devices in your project after the device exchange.
Refer to the S7-1200 System Manual for complete details on the V4.0 features.
See also
Changing a device (Page 74)