8.3 PID_Compact instruction ErrorBit parameters
Easy Book
178 Manual, 03/2014, A5E02486774-AF
ErrorBit (DW#16#...)
Description
20000 Invalid value at the SubstituteValue tag: Value has an invalid number
format.
PID_Compact uses the output value low limit as the output value.
Note: If automatic mode was active before the error occurred,
ActivateRecoverMode = TRUE, and the error is no longer pending,
PID_Compact switches back to automatic mode.
40000 Invalid value at the Disturbance parameter: Value has an invalid number
format.
Note: If automatic mode was active and ActivateRecoverMode = FALSE
before the error occurred, Disturbance is set to zero. PID_Compact remains
in automatic mode.
Note: If pre-
tuning or fine tuning mode was active and ActivateRecoverMode
= TRUE before the error occurred, PID_Compact switches to the operating
mode that is saved in the Mode parameter. If Disturbance in the current
phase has no effect on the output value, tuning is not canceled.
1
Note: If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE,
PID_Compact remains in automatic mode.
2
Note: If pre-tuning or fine tuning mode was active before the error occurred and
ActivateRecoverMode = TRUE, PID_Compact switches to the operating mode that is saved in the
Mode parameter.
3
Note: If automatic mode was active before the error occurred and ActivateRecoverMode = TRUE,
PID_Compact outputs the configured substitute output value. As soon as the error is no longer
pending, PID_Compact switches back to automatic mode.
4
Note: If ActivateRecoverMode = TRUE before the error occurred, PID_Compact cancels the tuning
and switches to the operating mode that is saved in the Mode parameter.