User Manual

Technical specifications
A.9 Communication interfaces
Easy Book
330 Manual, 03/2014, A5E02486774-AF
Technical specifications
Power supply / external
minimum
maximum
24 V
19.2 V
28.8 V
Current consumption (typical)
from 24 V DC
from the S7-1200 backplane bus
100 mA
0 mA
Effective power loss (typical)
from 24 V DC
from the S7-1200 backplane bus
2.4 W
0 W
Power supply 24 VDC / external
Min. cable cross section
Max. cable cross section
Tightening torque of the screw terminals
min.: 0.14 mm
2
(AWG 25)
max.: 1.5 mm
2
(AWG 15)
0.45 Nm (4 lb-in)
Dimensions and weights
Width
Height
Depth
30 mm
100 mm
75 mm
Weight
Net weight
Weight including packaging
134 g
171 g
*
)
The current load of an external consumer connected between VP (pin 6) and DGND (pin 5) must not exceed a maximum
of 15 mA (short-circuit proof) for bus termination.
PROFIBUS interface
Table A- 62 Pinout of the D-sub socket
Pin
Description
Pin
Description
1 - not used - 6 VP: Power supply +5 V only for bus
terminating resistors;
not for supplying external devices
2
- not used -
7
- not used -
3
RxD/TxD-P: Data line B
8
RxD/TxD-N: Data line A
4
CNTR-P: RTS
9
- not used -
5 DGND: Ground for data signals
and VP
Housing Ground connector