User Manual

Technical specifications
A.9 Communication interfaces
Easy Book
Manual, 03/2014, A5E02486774-AF
335
Table A- 65 Transmitter and receiver
Technical data
CB 1241 RS485
Type
RS485 (2-wire half-duplex)
Common mode voltage range
-7 V to +12 V, 1 second, 3 VRMS continuous
Transmitter differential output voltage 2 V min. at R
L
= 100 Ω
1.5 V min. at R
L
= 54 Ω
Termination and bias 10K to +5 V on B, RS485 Pin 3
10K to GND on A, RS485 Pin 4
Optional termination Short Pin TB to Pin T/RB, effective termination impedance is 127 Ω,
connects to RS485 Pin 3
Short Pin TA to Pin T/RA, effective termination impedance is 127 Ω,
connects to RS485 Pin 4
Receiver input impedance
5.4K Ω min. including termination
Receiver threshold/sensitivity
+/- 0.2 V min., 60 mV typical hysteresis
Isolation
RS485 signal to chassis ground
RS485 signal to CPU logic common
500 VAC, 1 minute
Cable length, shielded
1000 m max.
Baud rate 300 baud, 600 baud, 1.2 kbits, 2.4 kbits, 4.8 kbits, 9.6 kbits (default),
19.2 kbits, 38.4 kbits, 57.6 kbits, 76.8 kbits, 115.2 kbits,
Parity No parity (default), even, odd, Mark (parity bit always set to 1),
Space (parity bit always set to 0)
Number of stop bits
1 (default), 2
Flow control
Not supported
Wait time
0 to 65535 ms
Table A- 66 Power supply
Technical data
CB 1241 RS485
Power loss (dissipation)
1.5 W
Current consumption (SM Bus), max.
50 mA
Current consumption (24 VDC) max.
80 mA