Datasheet

I²t, max. 1 A²·s
Built-in incoming fuse T 1.6 A/250 V (not accessible)
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: 3 A, characteristic C
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.2 %
Residual ripple peak-peak, max. 50 mV
Residual ripple peak-peak, typ. 5 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 150 mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 20 mV
Product feature / output voltage adjustable No
Output voltage setting -
Status display Green LED for 24 V OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 2 s
Voltage rise, typ. 10 ms
Rated current value Iout rated 2 A
Current range 0 … 2 A
delivered active power / typ. 48 W
short-term overload current / at short-circuit during run-up / typical 9 A
Duration of overloading ability for excess current / on short-circuiting
during the start-up
90 ms
short-term overload current / at short-circuit during operation / typical 9 A
Duration of overloading ability for excess current / on short-circuiting
during the operational phase
90 ms
Parallel switching for enhanced performance Yes
Efficiency
Efficiency at Vout rated, Iout rated, approx. 84 %
Power loss at Vout rated, Iout rated, approx. 9 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 0.8 %
Load step setting time 50 to 100%, typ. 0.5 ms
Load step setting time 100 to 50%, typ. 0.5 ms
Setting time / maximum 1 ms
Protection and monitoring
Output overvoltage protection Additional control loop, shutdown at < 28.8 V, automatic restart
6ES7307-1BA01-0AA0
Page 2/ 10/01/2012
subject to modifications
© Copyright Siemens AG 2012
4