Datasheet

Current limitation 2.2 … 2.6 A
Characteristic feature of the output / short-circuit protected Yes
Short-circuit protection Electronic shutdown, automatic restart
Enduring short circuit current / Effective level / maximum 2 A
Overload/short-circuit indicator -
Safety
Primary/secondary isolation Yes
Potential separation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
stray current / maximum 3.5 mA
stray current / typical 0.5 mA
CE mark Yes
UL/CSA approval Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289, UL 1604
Class I Div. 2 Group A, B, C, D, File E330455
Explosion protection ATEX (EX) II 3G Ex nA II T4; UL 1604 Class I, Div. 2, Group ABCD
FM approval Class I, Div. 2, Group ABCD, T4
CB approval No
Marine approval In S7-300 system
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2
Operating data
Ambient temperature / in operation 0 … 60 °C
• Note with natural convection
Ambient temparature / on transport -40 … +85 °C
Ambient temparature / in storage -40 … +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections / Supply input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely
stranded
Connections / Output L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
Connections / Auxiliary -
Width / of the housing 40 mm
Height / of the housing 125 mm
Depth / of the housing 120 mm
6ES7307-1BA01-0AA0
Page 3/ 10/01/2012
subject to modifications
© Copyright Siemens AG 2012
4