Data sheet 6ES7313-6CG04-0AB0 SIMATIC S7-300, CPU 313C-2 DP Compact CPU with MPI, 16 DI/16 DO, 3 high-speed counters (30 kHz), integrated DP interface, Integr. power supply 24 V DC, work memory 128 KB, Front connector (1x 40-pole) and Micro Memory Card required General information HW functional status 01 Firmware version V3.3 Engineering with ● Programming package STEP 7 V5.5 + SP1 or higher or STEP 7 V5.
— Reverse polarity protection Yes Digital outputs — Rated value (DC) 24 V — Reverse polarity protection No Input current Current consumption (rated value) 800 mA Current consumption (in no-load operation), typ. 110 mA Inrush current, typ. 5A I²t 0.7 A²·s Digital inputs ● from load voltage L+ (without load), max. 80 mA Digital outputs ● from load voltage L+, max. 50 mA Power loss Power loss, typ.
● Number, max. 1 024; Number range: 0 to 7999 ● Size, max. 64 kbyte ● Number, max. 1 024; Number range: 0 to 7999 ● Size, max. 64 kbyte ● Description see instruction list ● Size, max.
— preset No retentivity Time range — lower limit 10 ms — upper limit 9 990 s IEC timer ● present Yes ● Type SFB ● Number Unlimited (limited only by RAM capacity) Data areas and their retentivity retentive data area in total All, max. 64 KB Flag ● Number, max.
— of which central 1 008 Analog channels ● Inputs — of which central ● Outputs — of which central 1 015 248 1 015 248 Hardware configuration Number of expansion units, max. 3 Number of DP masters ● integrated 1 ● via CP 4 Number of operable FMs and CPs (recommended) ● FM 8 ● CP, PtP 8 ● CP, LAN 6 Rack ● Racks, max. 4 ● Modules per rack, max. 8; In rack 3 max.
Digital inputs Number of digital inputs ● of which inputs usable for technological functions 16 12 integrated channels (DI) 16 Input characteristic curve in accordance with IEC 61131, type 1 Yes Number of simultaneously controllable inputs horizontal installation — up to 40 °C, max. 16 — up to 60 °C, max. 8 vertical installation — up to 40 °C, max. 8 Input voltage ● Rated value (DC) 24 V ● for signal "0" -3 to +5V ● for signal "1" +15 to +30V Input current ● for signal "1", typ.
Controlling a digital input Yes Switching capacity of the outputs ● on lamp load, max. 5W Load resistance range ● lower limit 48 Ω ● upper limit 4 kΩ Output voltage ● for signal "1", min. L+ (-0.8 V) Output current ● for signal "1" rated value 500 mA ● for signal "1" permissible range, min. 5 mA ● for signal "1" permissible range, max. 0.6 A ● for signal "1" minimum load current 5 mA ● for signal "0" residual current, max. 0.
— permissible quiescent current (2-wire sensor), max. 1.5 mA Interfaces Number of industrial Ethernet interfaces 0 Number of PROFINET interfaces 0 Number of RS 485 interfaces 2; MPI and PROFIBUS DP Number of RS 422 interfaces 0 1. Interface Interface type Integrated RS 485 interface Physics RS 485 Isolated No Power supply to interface (15 to 30 V DC), max.
● Number of DP slaves, max. 124 Services — PG/OP communication Yes — Routing Yes — Global data communication No — S7 basic communication Yes; I blocks only — S7 communication Yes; Yes (only server; connection configured at one end) — S7 communication, as client No — S7 communication, as server Yes — Equidistance Yes — Isochronous mode No — SYNC/FREEZE Yes — Activation/deactivation of DP slaves Yes — Number of DP slaves that can be simultaneously activated/deactivated, max.
Transfer memory — Inputs 244 byte — Outputs 244 byte Communication functions PG/OP communication Yes Data record routing Yes Global data communication ● supported Yes ● Number of GD loops, max. 8 ● Number of GD packets, max. 8 ● Number of GD packets, transmitter, max. 8 ● Number of GD packets, receiver, max. 8 ● Size of GD packets, max. 22 byte ● Size of GD packet (of which consistent), max. 22 byte S7 basic communication ● supported Yes ● User data per job, max.
— adjustable for S7 basic communication, max. ● usable for routing 4 4; max. S7 message functions Number of login stations for message functions, max. 8; Depending on the configured connections for PG/OP and S7 basic communication Process diagnostic messages Yes simultaneously active Alarm-S blocks, max.
controlled positioning No integrated function blocks (closed-loop control) Yes; PID controller (see "Technological Functions" manual) PID controller Yes Number of pulse outputs 3; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual) Limit frequency (pulse) 2.
● User program protection/password protection Yes ● Block encryption Yes; With S7 block Privacy Dimensions Width 80 mm Height 125 mm Depth 130 mm Weights Weight, approx.