Data Sheet
● lower limit
48Ω
● upper limit
3kΩ
Output voltage
● for signal "1", min.
L+ (-0.8 to -1.6 V)
Output current
● for signal "1" rated value
0.5A
● for signal "1" minimum load current
10mA
● for signal "0" residual current, max.
0.5mA
Switching frequency
● with resistive load, max.
100Hz
● with inductive load, max.
2Hz
● on lamp load, max.
10Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.
4A
— up to 60 °C, max.
3A
vertical installation
— up to 40 °C, max.
4A
Cable length
● shielded, max.
1000m
● unshielded, max.
600m
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Alarms
● Diagnostic alarm
Yes; Parameterizable
Diagnostic messages
● Wire-break
Yes
● Short-circuit
Yes
● Fuse blown
No
● missing load voltage
Yes
Diagnostics indication LED
● Rated load voltage PWR (green)
No
● Fuse OK FSG (green)
No
● Group error SF (red)
Yes
● Status indicator digital output (green)
Yes; per channel
● Channel fault indicator F (red)
Yes
Potential separation
Potential separation digital outputs
● between the channels, in groups of
8
● between the channels and backplane bus
Yes; Optocoupler
6ES7322-8BF00-0AB0 Subject to change without notice
Page 2/
3
09/13/2019 © Copyright Siemens