Data sheet 6ES7416-3FS07-0AB0 SIMATIC S7-400, CPU416F-3 PN/DP Central processing unit with: Work memory 16 MB, (8 MB code, 8 MB data), interfaces 1st interface MPI/DP 12 Mbit/s, (X1), 2nd interface Ethernet/PROFINET (X5) 3rd interface IF 964-DP plug-in (IF1) General information Product type designation CPU 416F-3 PN/DP HW functional status 01 Firmware version V7.0 Engineering with ● Programming package STEP 7 V5.
Power loss Power loss, typ. 6.5 W Power loss, max. 8W Memory Type of memory RAM Work memory ● integrated 16 Mbyte ● integrated (for program) 8 Mbyte ● integrated (for data) 8 Mbyte ● expandable No Load memory ● expandable FEPROM Yes; with Memory Card (FLASH) ● expandable FEPROM, max. 64 Mbyte ● integrated RAM, max. 1 Mbyte ● expandable RAM Yes; with Memory Card (RAM) ● expandable RAM, max.
● Size, max. 64 kbyte ● Number, max. see instruction list ● Size, max.
Time range — lower limit 10 ms — upper limit 9 990 s IEC timer ● present Yes ● Type SFB ● Number Unlimited (limited only by RAM capacity) Data areas and their retentivity retentive data area in total Total working and load memory (with backup battery) Flag ● Number, max. 16 kbyte; Size of bit memory address area ● Retentivity available Yes ● Retentivity preset MB 0 to MB 15 ● Number of clock memories 8; in 1 memory byte Local data ● adjustable, max.
Hardware configuration Number of expansion units, max. 21 connectable OPs 95 Multicomputing Yes; 4 CPUs max. (with UR1 or UR2) Interface modules ● Number of connectable IMs (total), max. 6 ● Number of connectable IM 460s, max. 6 ● Number of connectable IM 463s, max. 4; IM 463-2 Number of DP masters ● integrated 1 ● via CP 10; CP 443-5 Extended ● via IM 467 4 ● Mixed mode IM + CP permitted No; IM 467 cannot be used jointly with CP 443-5 Ext.
Clock synchronization ● supported Yes ● to MPI, master Yes ● to MPI, slave Yes ● to DP, master Yes ● to DP, slave Yes ● in AS, master Yes ● in AS, slave Yes ● on Ethernet via NTP Yes; As client ● to IF 964 DP Yes Time difference in system when synchronizing via ● Ethernet, max. 10 ms ● MPI, max.
● Number of connections, max. 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 ● Transmission rate, max. 12 Mbit/s ● Number of DP slaves, max.
— S7 communication Yes — S7 communication, as client Yes — S7 communication, as server Yes — Direct data exchange (slave-to-slave communication) No — DPV1 No Transfer memory — Inputs 244 byte — Outputs 244 byte 2.
— Open IE communication Yes — Shared device Yes — Prioritized startup Yes — Number of IO devices with prioritized startup, max. 32 — Number of connectable IO Devices, max. 256 — Of which IO devices with IRT, max. 64 — of which in line, max. 64 — Number of IO Devices with IRT and the option "high flexibility" 256 — of which in line, max. 61 — Number of connectable IO Devices for RT, max. 256 — of which in line, max.
— Number of IO Controllers with shared device, max. 2 Transfer memory — Inputs, max. 1 440 byte; Per IO Controller with shared device — Outputs, max. 1 440 byte; Per IO Controller with shared device Submodules — Number, max. 64 — User data per submodule, max. 1 024 byte PROFINET CBA ● acyclic transmission Yes ● cyclic transmission Yes Open IE communication ● Number of connections, max.
— SYNC/FREEZE Yes — Activation/deactivation of DP slaves Yes — Direct data exchange (slave-to-slave communication) Yes — DPV0 Yes — DPV1 Yes Address area — Inputs, max. 8 kbyte — Outputs, max. 8 kbyte User data per DP slave — User data per DP slave, max. 244 byte — Inputs, max. 244 byte — Outputs, max. 244 byte — Slots, max. 244 — per slot, max. 128 byte PROFIBUS DP slave ● Number of connections 32 ● GSD file http://support.automation.siemens.
— Data length, max. 32 kbyte — several passive connections per port, supported Yes ● ISO-on-TCP (RFC1006) Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs — Number of connections, max. 94 — Data length, max. 32 kbyte; 1452 bytes via CP 443-1 Adv. ● UDP Yes; via integrated PROFINET interface and loadable FBs — Number of connections, max. 94 — Data length, max.
● as server Yes ● as client Yes ● User data per job, max. 64 kbyte ● User data per job (of which consistent), max. 462 byte; 1 variable S5 compatible communication ● supported Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 ● User data per job, max. 8 kbyte ● User data per job (of which consistent), max. 240 byte ● Number of simultaneous AG-SEND/AG-RECV orders per CPU, max.
— Data length of all incoming interconnections, max. 4 800 byte — Data length of all outgoing interconnections, max. 4 800 byte — Data length per connection, max. 450 byte HMI variables via PROFINET (acyclic) — Number of stations that can log on for HMI variables (PN OPC/iMap) 2x PN OPC/1x iMap — HMI variable updating 500 ms — Number of HMI variables 1 500 — Data length of all HMI variables, max. 48 000 byte PROFIBUS proxy functionality — supported Yes; 32 PROFIBUS slaves max.
● Number of instances for alarm 8 and S7 communication blocks, max. 4 000 ● preset, max. 600 Process control messages Yes Number of archives that can log on simultaneously (SFB 37 AR_SEND) 32 Number of messages ● overall, max. 1 024 ● in 100 ms grid, max. 128 ● in 500 ms grid, max. 512 ● in 1000 ms grid, max. 1 024 Number of additional values ● with 100 ms grid, max. 1 ● with 500, 1000 ms grid, max.
EAC (formerly Gost-R) Yes Use in hazardous areas ● ATEX ATEX II 3G Ex nA IIC T4 Gc Ambient conditions Ambient temperature during operation ● min. 0 °C ● max.
● User program protection/password protection Yes ● Block encryption Yes; With S7 block Privacy Dimensions Width 50 mm Height 290 mm Depth 219 mm Weights Weight, approx.