Data Sheet
— S7 communication
Yes
— S7 communication, as client
Yes
— S7 communication, as server
Yes
— Direct data exchange (slave-to-slave
communication)
No
— DPV1
No
Transfer memory
— Inputs
244byte
— Outputs
244byte
2. Interface
Interface type PROFINET
Physics Ethernet RJ45
Isolated Yes
automatic detection of transmission rate Yes; Autosensing
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported Yes; Assignment by higher-level IO-Controller or by the user
program with SFB104 "IP_CONF"
Number of connection resources 96
Interface types
● Number of ports
2
● integrated switch
Yes
Media redundancy
● supported
Yes
● Switchover time on line break, typ.
200ms
● Number of stations in the ring, max.
50
Protocols
● PROFINET IO Controller
Yes
● PROFINET IO Device
Yes
● PROFINET CBA
Yes
● PROFIBUS DP master
No
● PROFIBUS DP slave
No
● Open IE communication
Yes
● Web server
Yes
● Point-to-point connection
No
PROFINET IO Controller
● Transmission rate, max.
100Mbit/s
Services
— PG/OP communication
Yes
— S7 routing
Yes
— S7 communication
Yes
— Isochronous mode
Yes; Only with IRT and the High Performance option