Data Sheet
● for signal "1", min.
L+ (-0.3 V)
Output current
● for signal "1" rated value
0.5A
● for signal "1" permissible range, min.
5mA
● for signal "1" permissible range, max.
0.6A
● for signal "0" residual current, max.
0.3mA
Switching frequency
● with resistive load, max.
100Hz
● with inductive load, max.
0.5Hz
Total current of the outputs (per group)
all mounting positions
— up to 60 °C, max.
2A; 8 adjacent outputs each
Cable length
● shielded, max.
1000m
● unshielded, max.
600m
Interrupts/diagnostics/status information
Diagnostics function No
Potential separation
Potential separation digital outputs
● between the channels, in groups of
32
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 500 V DC
Dimensions
Width 25mm
Height 290mm
Depth 210mm
Weights
Weight, approx. 600g
last modified:
09/11/2019
6ES7422-1BL00-0AA0 Subject to change without notice
Page 2/
2