Data Sheet

Rated value at 48 V DC 1.5A
Rated value at 60 V DC 1.2A
Output current
Short-circuit protection Yes
Power
Infeed power to the backplane bus 60W
Power loss
Power loss at nominal rating conditions 12W
Interrupts/diagnostics/status information
Status indicator Yes
Potential separation
primary/secondary Yes; Electrical isolation for 230 V AC (reinforced isolation)
Isolation
Isolation tested with 2 500 V DC/2 s (routine test)
EMC
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5
Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV
(acc. to IEC 61000-4-5; 1995; surge asymm.), no external
protective circuit required
Degree and class of protection
Degree of protection acc. to EN 60529 IP20
Equipment protection class I, with protective conductor
Dimensions
Width 70mm
Height 147mm
Depth 129mm
Weights
Weight, approx. 600g
last modified:
09/11/2019
6ES7505-0RA00-0AB0 Subject to change without notice
Page 2/
2
09/13/2019 © Copyright Siemens