Data sheet 6ES7511-1FK02-0AB0 SIMATIC S7-1500F, CPU 1511F-1 PN, CENTRAL PROCESSING UNIT WITH WITH WORKING MEMORY 225 KB FOR PROGRAM AND 1 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 60 NS BIT-PERFORMANCE, SIMATIC MEMORY CARD NECESSARY General information Product type designation CPU 1511F-1 PN HW functional status FS01 Firmware version V2.6 Product function ● I&M data Yes; I&M0 to I&M3 Engineering with ● STEP 7 TIA Portal configurable/integrated as of version V15.1 (FW V2.
Type of supply voltage 24 V DC permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Yes Mains buffering ● Mains/voltage failure stored energy time 5 ms ● Repeat rate, min. 1s Input current Current consumption (rated value) 0.7 A Current consumption, max. 0.95 A Inrush current, max. 1.9 A; Rated value I²t 0.02 A²·s Power Infeed power to the backplane bus 10 W Power consumption from the backplane bus (balanced) 5.
FB ● Number range 0 ... 65 535 ● Size, max. 150 kbyte ● Number range 0 ... 65 535 ● Size, max. 150 kbyte ● Size, max.
Retentive data area (incl. timers, counters, flags), max. 128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB Extended retentive data area (incl. timers, counters, flags), max. 1 Mbyte; When using PS 6 0W 24/48/60 V DC HF Flag ● Number, max.
Time of day Clock ● Type Hardware clock ● Backup time 6 wk; At 40 °C ambient temperature, typically ● Deviation per day, max. 10 s; Typ.: 2 s Operating hours counter ● Number 16 Clock synchronization ● supported Yes ● in AS, master Yes ● in AS, slave Yes ● on Ethernet via NTP Yes Interfaces Number of PROFINET interfaces 1 1.
— Of which IO devices with IRT, max. 64 — Number of connectable IO Devices for RT, max. 128 — of which in line, max. 128 — Number of IO Devices that can be simultaneously activated/deactivated, max. 8; in total across all interfaces — Number of IO Devices per tool, max.
Interface types RJ 45 (Ethernet) ● 100 Mbps Yes ● Autonegotiation Yes ● Autocrossing Yes ● Industrial Ethernet status LED Yes Protocols Number of connections ● Number of connections, max.
● User data per job, max. See online help (S7 communication, user data size) Open IE communication ● TCP/IP Yes — Data length, max. 64 kbyte — several passive connections per port, supported Yes ● ISO-on-TCP (RFC1006) — Data length, max. ● UDP Yes 64 kbyte Yes — Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast — UDP multicast Yes; Max.
— Number of registerable method calls of OPC_UA_MethodCall, max. 100 — Number of inputs/outputs when calling OPC_UA_MethodCall, max. 20 ● OPC UA server Yes; Data access (read, write, subscribe), method call, custom address space — Application authentication Yes — Security policies Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 — User authentication "anonymous" or by user name & password — Number of sessions, max. 32 — Number of accessible variables, max.
● Number of alarms for motion technology objects 80 Test commissioning functions Joint commission (Team Engineering) Yes; Parallel online access possible for up to 5 engineering systems Status block Yes; Up to 8 simultaneously (in total across all ES clients) Single step No Number of breakpoints 8 Status/control ● Status/control variable Yes ● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters ● Number of variables, max. — of which status variables, max.
— per output cam 20 — per cam track 160 — per probe 40 ● Positioning axis — Number of positioning axes at motion control cycle of 4 ms (typical value) 5 — Number of positioning axes at motion control cycle of 8 ms (typical value) 10 Controller ● PID_Compact Yes; Universal PID controller with integrated optimization ● PID_3Step Yes; PID controller with integrated optimization for valves ● PID-Temp Yes; PID controller with integrated optimization for temperature Counting and measuring ● High-s
— STL Yes — SCL Yes — GRAPH Yes Know-how protection ● User program protection/password protection Yes ● Copy protection Yes ● Block protection Yes Access protection ● Password for display Yes ● Protection level: Write protection Yes; Specific write protection both for Standard and for Failsafe ● Protection level: Read/write protection Yes ● Protection level: Complete protection Yes Cycle time monitoring ● lower limit adjustable minimum cycle time ● upper limit adjustable maximum cycle