Data Sheet
Number of simultaneously active program alarms
● Number of program alarms
300
● Number of alarms for system diagnostics
100
● Number of alarms for motion technology
objects
80
Test commissioning functions
Joint commission (Team Engineering) Yes; Parallel online access possible for up to 5 engineering
systems
Status block Yes; Up to 8 simultaneously (in total across all ES clients)
Single step No
Number of breakpoints 8
Status/control
● Status/control variable
Yes
● Variables
Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters
● Number of variables, max.
— of which status variables, max.
200; per job
— of which control variables, max.
200; per job
Forcing
● Forcing
Yes
● Forcing, variables
Peripheral inputs/outputs
● Number of variables, max.
200
Diagnostic buffer
● present
Yes
● Number of entries, max.
1000
— of which powerfail-proof
500
Traces
● Number of configurable Traces
4; Up to 512 KB of data per trace are possible
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED
Yes
● ERROR LED
Yes
● MAINT LED
Yes
● Monitoring of the supply voltage (PWR-LED)
Yes
● Connection display LINK TX/RX
Yes
Supported technology objects
Motion Control Yes; Note: The number of axes affects the cycle time of the PLC
program; selection guide via the TIA Selection Tool or SIZER
● Number of available Motion Control resources
for technology objects (except cam disks)
800
● Required Motion Control resources
— per speed-controlled axis
40
6ES7512-1DK01-0AB0 Subject to change without notice