Data Sheet

● Backup time
6wk; At 40 °C ambient temperature, typically
● Deviation per day, max.
10s; Typ.: 2 s
Operating hours counter
● Number
16
Clock synchronization
● supported
Yes
● to DP, master
Yes; Via CM DP module
● to DP, slave
Yes; Via CM DP module
● in AS, master
Yes
● in AS, slave
Yes
● on Ethernet via NTP
Yes
Interfaces
Number of PROFINET interfaces 1
Number of PROFIBUS interfaces 1; Via CM DP module
With optical interface Yes; via BusAdapter
1. Interface
Interface types
● Number of ports
3; 1. integr. + 2. via BusAdapter
● integrated switch
Yes
● RJ 45 (Ethernet)
Yes; X1 P3; opt. X1 P1 and X1 P2 via BusAdapter BA 2x RJ45
● BusAdapter (PROFINET)
Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x
SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45,
BA LC / FC
Protocols
● IP protocol
Yes; IPv4
● PROFINET IO Controller
Yes
● PROFINET IO Device
Yes
● SIMATIC communication
Yes
● Open IE communication
Yes
● Web server
Yes
● Media redundancy
Yes; MRP Automanager according to IEC 62439-2 Edition 2.0
PROFINET IO Controller
Services
— PG/OP communication
Yes
— S7 routing
Yes
— Isochronous mode
Yes
— Open IE communication
Yes
— IRT
Yes
— MRP
Yes; as MRP redundancy manager and/or MRP client; max.
number of devices in the ring: 50
— MRPD
Yes; Requirement: IRT
6ES7512-1DK01-0AB0 Subject to change without notice
Page 5/
12
09/13/2019 © Copyright Siemens