Data Sheet

— PROFIenergy
Yes
— Prioritized startup
Yes; Max. 32 PROFINET devices
— Number of connectable IO Devices, max.
128; In total, up to 512 distributed I/O devices can be connected
via AS-i, PROFIBUS or PROFINET
— Of which IO devices with IRT, max.
64
— Number of connectable IO Devices for RT,
max.
128
— of which in line, max.
128
— Number of IO Devices that can be
simultaneously activated/deactivated, max.
8; in total across all interfaces
— Number of IO Devices per tool, max.
8
— Updating times
The minimum value of the update time also depends on
communication share set for PROFINET IO, on the number of IO
devices, and on the quantity of configured user data
Update time for IRT
— for send cycle of 250 µs
250 μs to 4 ms; Note: In the case of IRT with isochronous mode,
the minimum update time of 500 µs of the isochronous OB is
decisive
— for send cycle of 500 µs
500 µs to 8 ms
— for send cycle of 1 ms
1 ms to 16 ms
— for send cycle of 2 ms
2 ms to 32 ms
— for send cycle of 4 ms
4 ms to 64 ms
— With IRT and parameterization of "odd"
send cycles
Update time = set "odd" send clock (any multiple of 125 µs: 375
µs, 625 µs ... 3 875 µs)
Update time for RT
— for send cycle of 250 µs
250 µs to 128 ms
— for send cycle of 500 µs
500 µs to 256 ms
— for send cycle of 1 ms
1 ms to 512 ms
— for send cycle of 2 ms
2 ms to 512 ms
— for send cycle of 4 ms
4 ms to 512 ms
PROFINET IO Device
Services
— PG/OP communication
Yes
— S7 routing
Yes
— Isochronous mode
No
— Open IE communication
Yes
— IRT
Yes
— MRP
Yes; as MRP redundancy manager and/or MRP client; max.
number of devices in the ring: 50
— MRPD
Yes; Requirement: IRT
— PROFIenergy
Yes; per user program
— Shared device
Yes
6ES7512-1DK01-0AB0 Subject to change without notice
Page 6/
12
09/13/2019 © Copyright Siemens